ICS / OT Operator Skill Catalog
Industrial engagements are not application security with longer rules of engagement — they are a different discipline. A miswritten Modbus coil on a real plant kills people. This catalog is read-mostly by default; every write-scope skill carries an explicit safety gate.
Hard rules
- No writes without OPPLAN.safety_critical confirmation. The
middleware refuses writes when the active OPPLAN objective does not
carry
safety_critical_confirmed=true. Bypass requires operator signature in/workspace/safety-attestation.txt. - Read-only protocol discovery first. Identify what's on the wire before any active probing. Many ICS protocols are unauthenticated; a single malformed read can crash an old PLC.
- Out-of-band physical safety. The blue team includes plant ops.
A ConOps with
blue_team.plant_ops_phoneis mandatory for engagements on active production lines.
Playbooks
Inline technique reference — not separately loadable skills. The entries below are summarized here for direct use; there is no separate
SKILL.mdto open for each. Do NOT call the skill loader on them — apply the technique with your tools using this summary and the protocol assessment guidance in this file.
| Technique | Use for |
|---|---|
| modbus-discovery | Read-only Modbus TCP/RTU enumeration, function code 3/4 polling |
| modbus-write | GATED Write coils / registers; safety gate enforced |
| bacnet-discovery | BACnet/IP Who-Is, object enumeration, device profile |
| s7comm | Siemens S7 / S7Comm Plus enumeration via Snap7 / python-snap7 |
| dnp3 | DNP3 outstation / master discovery; integrity poll |
| opcua | OPC-UA browse, anonymous auth check, certificate analysis |
| hmi-web | HMI web stacks (Wonderware, Iconics, Schneider) — known CVEs |
| engineering-software | TIA Portal / Studio 5000 / Unity Pro project extraction |
Protocol assessment
- Passive observation: tap a SPAN port if available. Identify protocols
on the wire (
tshark -Y modbus || tshark -Y bacnet || ...). - Network-layer discovery: nmap with
-sV --script modbus-discover,bacnet-info,s7-info,dnp3-info(NSE scripts ship in Kali by default; some are slow — set-T2for production networks). - Function-code-3 polling: read holding registers from every Modbus
device discovered. Log register maps to the knowledge graph as
:Servicenodes withprotocol=modbus. - Identify the safety integrity level (SIL) of any device touched. SIL 3+ devices NEVER get write probes without plant-ops sign-off.
- Engineering software attack path: if you can reach the engineering workstation, extract the project archive (.s7p, .acd, .stp). The project file is the crown jewel — it reveals the entire process model.
Detection gap
ICS networks rarely have host-based detection on PLCs/RTUs themselves — the detection stack lives on the engineering workstation, the historian, and any IT/OT gateway. Relevant Sigma detection patterns include:
- Function-code anomalies (write to coils outside normal ranges).
- Connection sources outside the documented MES/SCADA IP set.
- TIA Portal / Studio 5000 project download events.
Out of scope by default
Active glitching of PLC firmware; firmware upload to PLCs; safety
controller writes — all of these require an explicit RoE annex signed
by the asset owner. The default ICS RoE template in soundwave/ includes
this annex skeleton.
常见问题
为什么默认只读?
目录指出,写错的指令可能损害工厂,因此写入操作需要明确批准。
哪些人应该参与?
目录指出,对于正在运行的生产线,计划中应包括工厂运营人员。
涵盖哪些协议?
Modbus、BACnet、Siemens S7、DNP3 和 OPC UA 等。
详情
作者的原始描述
Use when the target is an industrial control system or operational technology network running Modbus, BACnet, S7Comm/S7Comm Plus, DNP3, OPC-UA, or any PLC/HMI/SCADA stack. Engagements MUST set RoE flag industrial_safety_critical=true; this catalog gates every write-scope operation behind explicit operator confirmation regardless of HITL middleware.
热度
- GitHub 星标
- 6.5k
- 排名
- #14091
- 许可证
- Apache-2.0
- 更新时间
- 2026/11/1
评论
- …